Voltage |
8 ranges: 0.3 V, 1 V, 3 V, 10 V, 30 V, 100 V, 300 V, 1000 V |
|
Frequency range |
|
|
DC, 0.1 Hz – 1 MHz |
Crest Factor |
|
|
3:1 at 50 % full scale (fs) |
Input Impedance |
|
|
1 MOhm |
Common Mode |
50 Hz/100 kHz |
|
160 dB/100 dB |
Standard accuracy 23°C; rms, mean, rectified mean; 0.3V typical
1 Hz-1 kHz                           ±(0.1 % rdg +0.1 % range)
DC, 1 kHz-10 kHz                    ±(0.2 % rdg +0.2 % range)
10 kHz-100 kHz                       ±(0.3 %/ range + 0.04 % /kHz rdg)
100 kHz-300 kHz                     ±(0.3 %/ range + 0.04 % /kHz rdg), typical |
Improved accuracy
±(0.05 % rdg + 0.07 % range) |
Current |
13 ranges: 1.5 mA, 5 mA, 15 mA, 50 mA, 150 mA, 500 mA, 1.5 A, 5 A; 1, 3, 10, 30, 100 A |
Max. 1 A, 5 A, 30 A, resp. |
Frequency range |
|
|
DC, 0.1 Hz-300 kHz / 1 MHz |
Crest Factor |
|
|
3:1 at 50 % full scale (fs) |
Common Mode |
50 Hz/100 kHz |
|
160 dB/120 dB |
Standard accuracy 23°C; 1 A-, 5 A-, shunt input              30 A input
1 Hz-1 kHz               ±(0.1 % rdg + 0.1 % rng)                 ±(0.1 % rdg + 0.1 % rng)DC, 1 kHz-10 kHz    ±(0.2 % rdg + 0.2 % rng)                 ±(0.7 % rdg + 0.2 % rng)10 kHz-100 kHz       ±(0.3 % range + 0.04 %/kHz rdg)    ±(0.3 % rng + 0.5 %/kHz rdg), typ100 kHz-300 kHz     ±(0.3 % range + 0.04 %/kHz rdg), typical |
Lowest ranges 1.5 mA, 15 mA,
1 A: typical.
Improved accuracy 1Hz-400 Hz
±(0.05 % rdg + 0.07 % range) |
Power
|
104 ranges corresponding to the products V x A. |
|
|
|
Frequency range |
|
|
DC, 0.1 Hz-300 kHz |
45 Hz-65 Hz
1 Hz-1 kHz
DC, 1 kHz-10 kHz 10 kHz-100 kHz(0.1 % rdg + 0.01 % range)
Add accuracy percentage figures of current and voltage,
+0.04 %/kHz PF |
PF= 0 to ±0.1 PF= 0 to ±1 PF= 0 to ±1 PF=1 |
Frequency |
0.1 Hz-400 kHz, V triggered; Accuracy ±0.1 %. |
|
|
|
Computed Values |
Accuracy; Reactive Power, Var=±(VA2-W2)1/2, Apparent Power: VA=Arms Vrms; Power Factor: PF=W/VA; Crest Factor: CF=Ap/Arms, Vp/Vrms: Form Factor: FF=At/Arms, Vt/Vrms; Impedance: Z=Vrms/Arms; Total Harm Dist: THD=(Irms2- Ifund2)1/2/Irms
|
Add accuracy percentage figures of values involved in computation. |
Integrator |
Energy, Charge; Accuracy |
Wh, Vah, Varh, Ah; Basic accuracy of integrated quantity. |
|
|
Harmonic Analysis |
Frequency range of fundamental           2.5 Hz-100 kHz |
|
|
|
|
Range of harmonic |
|
|
1-99 |
|
Accuracy, Harmonic current and voltage
2 Hz-1 kHz             ±(0.1 % rdg + 0.1 % range) 1 kHz-10 kHz         ±(0.5 % rdg + 0.5 % range)
10 kHz.-100 kHz    ±(0.7 % range + 0.1 %/kHz rdg), typical |
|
Display |
Blue liquid crystal graphic display with FL backlight              64×120 mm; 128 x 240 pixels
|
|
Power |
AC, 50-400 Hz; Fuse: Power
|
85 V-240 V; 2 A, 15 VA |
Dieletric Strength |
Inputs to case or power supply Line input to case
Input to Input |
2.5 kV/50 Hz/1 minute
1.5 kV/50 Hz/ 1 minute 4 kV/50 Hz/1 minute |
Dimension |
H x W x D; Weight |
|
|
150 x 235 x 320 mm; 4 kg |
Options |
IEEE-488-2, RS232, Centronics printer output
4 programmable analog outputs; single-, sum-, or average values 4 analog inputs 0-±5V, input impedance 200 kΩ
4 analog inputs, 0-±10 V, input impedance 200 kΩ Rack Mounting Kit
Windows Operating Software 95, 98, 2000, NT, XP; transformer-motor testing |
0-±5 V, accuracy 0.2 % 0-±5 V, accuracy 0.2 % 0-±10 V accuracy 0.2 % |
1.5mA-1A Inp/ Shunt Input |
1 A input Hi against ILo Shunt Hi                  Shunt Lo |
1 A input,   mA:    1.5, 5, 15, 50, 150, 500, 1500
Shunt input, mV:   60, 60Ö10, 600, 600VÖ10, 6000, 6000Ö10
Input impedance:Â Â 60k |
1 A input: set scaling to 0.1 Shunt input: 60 mV corresponds to 1.0000 A |